• F F 1, Empire Business Hub, Nr. Shukan Mall, Nr. Sola Water Tank, Science City Road, Sola, Ahmedabad - 380060

Heat Pump Modular Type V-III Series AJH072LALBH [3Phase]

Capacity

C 22.4 kW
H 25.0 kW

Features

Excellent energy saving

High design flexibility for various building air conditioning

Easy installation and maintenance

Efficiency in actual operation

Energy saving technology that boosted operation efficiency

Indoor Unit :

Outdoor Unit :

AJH090LALBH

Download :

Catalog

ote:
Specifications are based on the following conditions.
Cooling:
Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating:
Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length:
7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
When cooling operation will be conducted at outdoor air temperature below -5°C,
the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Power Source Phase 3-phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 22.4 kW
Heating 25.0 kW
Input Power Cooling 5.20 kW
Heating 5.17 kW
EER Cooling 4.31 W/W
COP Heating 4.84 W/W
Airflow Rate 11,100 m/³h
Sound Pressure Level*2 Cooling 56 dB(A)
Heating 58 dB(A)
Sound Power Level Cooling 77 dB(A)
Heating 80 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 7.5 kW
Heat Exchanger Fin Blue fin
Net Dimensions Height 1,690 mm
Width 930 mm
Depth 765 mm
Net Weight 252 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.7 kg
Connection Pipe Diameter Liquid 12.70 mm
Gas 22.22 mm
Operation Range Cooling -15 to 46 °CDB
Heating -20 to 21 °CDB